Features

  • 4 Chemical Feed Timers
  • One Point Calibration
  • DIN connections for I/O
  • Full 24 Month Warranty
  •  

    MB9300-9600 Series Controllers

    The MB9200 Series Controller is a microprocessor based controller for boiler systems. The controller provides the ability to accurately control the level of dissolved solids based on µS/cm on a timed, held or continuous sample basis. Select models provide the ability to control the alkalinity of system water in units of pH.

    Control Functions
    All continuously monitored sensor input functions (conductivity) will provide user definable set points for maintaining a specific value within the system for up to two boilers at the same time. Each set point will have a user definable differential as the control band, programmable high and low alarm points.

    Chemical Feed Timer
    The chemical feed timer shall be user selectable as any one of the following:
     

  • Percent - User will be able to select a percent "ON" time of a user defined "cycle" time.
     
  • Limit - Timer will run as controller bleeds until a user programmed "limit" time is met or the bleed is satisfied.
     
  • Percent of Post-Bleed - Timer will run for a user defined percentage of the bleed time after bleed is satisfied with a fail-safe user set maximum run time.
     
  • Pulse Timer - Timer initiated from dry contacting head water meter. User can define timer run time, water meter input and contact accumulation before timer initiation.
     
  • Cycle Timer - User will be able to cycle chemical on and off a specified number of times during during a 28 day-per-month calendar basis.
     
  • Slave Timer - Timer will turn on its output when one or more selected relays activate. The relays can be slaved in any combination.
     
  • Disabled - Timer can be totally deactivated.

    Remote Communications
    The controller shall have the optional capability of serial communications using PULSAworks software. The serial communications can occur either by direct RS232 port, or remotely via an optional internal modem. PULSAworks allows the user to access real-time system values and download data history files and save files to disk. History files may be viewed and printed in table or graph form, the graph form can be user customized. The optional internal modem allows the controller to perform alarm call back for alarm condition notification to a pager or computer running PULSAworks software.

  •  
    Data Sheets & Brochures
     BCS-002 - MB9300/9600
    (PDF - 81 KB)
     
    Install & Operations Manuals
     MB9300/9600 Manual
    (PDF - 2.4 MB)
     
    Product List
     PULSAtrol Product List
    (PDF - 928 KB)

    Jump To:   Pumps  |   Controllers  |   Process Control  |   Systems  |   Support

    ©2005 - Pulsafeeder, Inc.
    A Unit of the Idex Corporation

    Contact the Webmaster